Report!on PPV Trials
at Oxford Road, Preston, U.K.
10 –14 January, 2000
Richard Stott B.Eng (Hons),
Assistant
Divisional Officer
Lancashire Fire and Rescue
Service, U.K.
In
contrast to the above paragraph, it has been decided to utilise the terms
offensive and defensive in this report, to parallel the Home Office and LFRS,
with the following definitions(1);
Offensive -
ventilating close to the fire to have a direct effect on the fire itself.
·
To
improve knowledge and skills in the use of defensive ppv
·
To
further assess fan selection in terms of fan size
·
To
produce a comprehensive report, (including stills and video footage), to
assist in future training packages and the further development of operational
procedures.
·
To
provide realistic, live fire observation for personnel involved.
·
To
provide comprehensive data for use in risk assessments.

Plate
1. Oxford Road, Avenham
Each
fire experiment room was furnished with the type of materials that would be
expected with a real incident i.e. carpets, curtains, sofas, bedding etc.
Consequently, the trials were possibly the most realistic, in terms of fire
loading, to have been carried out to date in the U.K.
The
trials took place over five days. The chosen approach was to carry out each
scenario twice, once using standard fire fighting techniques, (defensive) and
once using offensive positive pressure ventilation.
The
results of these experiments demonstrated the need for a systematic
ventilation procedure when using ppv. It was found that any compartment where
an outside window was not opened was effectively sealed by the ppv, preventing
any smoke clearance. Where ppv was not used the compartment cleared gradually,
but this did not happen with ppv. The main conclusion from this experiment is
that if using ppv for smoke clearance, rooms should be cleared one at a time
and once a room is clear of smoke, the windows should then be closed. The
report!further concludes that these results were due to the limited flow from
the portable ventilation units and that ppv was not as effective in clearing
rooms with upwind windows.
Fire
Authorities in the UK have acknowledged the training requirement for ppv; two
metropolitan Brigades have conducted fire experiments to assess the training
implications and effectiveness of ppv.
Tyne
and Wear Metropolitan Fire Brigade acquired the use of two derelict
semi-detached properties; these were subsequently used for tactical
ventilation trials in real fire situations during November 1996. The
properties used were identical in construction and layout, which enabled fires
to be repeated and compared.
Cribs
were placed in various rooms within the houses and holes drilled in the walls
at various heights to facilitate thermocouples. Temperature readings for all
the exercises were recorded and used to compare the effect of ppv in different
locations of the houses. Wooden pallets, straw, diesel and paraffin produced
the heat and smoke for the experiments with maximum temperatures reaching
around 800°C.
The
experiments from Tyne and Wear are summarised as follows (6):
·
Experiments carried out indicated ppv
would overcome wind strengths of 8-10m/s, the experiments carried out by the
experimental unit at Moreton showed ppv to be ineffective against a 2m/s wind.
·
Ppv did not seriously intensify or
spread a fire however some localised flaming did occur.
·
Ppv improves visibility in a short time
scale.
·
Ppv reduces temperatures dramatically
in a short period of after application.
·
Effective use of ppv improves the
working environment and reduces the risk of flashover.
The
Tyne and Wear report!recommends the defensive use of ppv and appears positive
regarding the use of ppv offensively.
Equipment
from the University Of Central Lancashire was used to measure temperatures,
gas compositions and fire growth in a similar manner to the Tyne and Wear
experiments. Video cameras erected outside the buildings observed the smoke
movement from the exhaust points whilst a thermal imaging camera was used to
show heat transfer and fire spread internally.
The
same criticism can be applied to each of the tests carried out i.e. it cannot
be concluded that ppv accelerated the fire any more than natural ventilation
alone would achieve.
During
all the tests a visible ‘flashback’ was reported on application of ppv.
The timing of this event for each test is unclear and no evidence is apparent
on the graphs. No reference had been made to this effect before and
consequently it is an interesting area for consideration.
There
are a number of possible reasons for this effect:
| The fire may be undergoing
transition from growth to fully developed, this transition is rapid; the
fire wants a large volume of oxygen which results in lengthened flames.
The fire nearly always becomes ventilation controlled at this stage. | |
| The fire compartment
pressure due to buoyancy is in excess of that in the doorway. | |
| There is too restrictive a
vent to outside; the fire had nowhere else to go. | |
| The fire was affected by
wind from outside. |
The
data from Tyne and Wear does highlight a small localised increase in
temperatures after ppv application, but does not mention the possibility of a
‘flashback’ on initial application, the report!does acknowledge the
potential danger of offensive use.
In
July 1998, Tyne and Wear Fire Brigade carried out a further set of trials at
the Fire Service College. The trials were conducted in conjunction with the
Fire Experimental Unit of the Home Office. The brief for these tests was to
establish the effects of ppv on a casualty situated between the fire and the
vent, and the effect of ppv on fire spread, two issues perceived at the time
to be holding ppv use back.
The
report(8) of the trials, produced by the Fire Research and
Development Group, concludes; ‘ppv produced no measurable difference in fire
spread from that observed under natural ventilation alone. However
ventilation, whether natural or forced, did appear to increase fire spread.’
This
was an interesting conclusion which again conflicts with the findings from
GMC.
Note:
the performance of positive pressure ventilation fans has improved
rapidly since their inception. Many of the early trials used fans that were of
low output and consequently some results may be misleading.
The
properties used for the trials were a connected block of single-storey, two and
three bedroom flats, built circa 1970. The block was scheduled for demolition
the week following the trials. The properties had been donated for use by
Collingwood Housing Association.
The
construction of the properties was mainly of concrete, which proved ideal for
repeatable experiments.
Plan
drawings of the properties are included in Appendix A
2.2
Equipment and Technical Apparatus
Appliances
and general firefighting equipment was provided by Lancashire Fire and Rescue
Service.
Positive
pressure ventilation fans were supplied by FSE Ltd. The company supplied a range
of fans for use but for consistency the same fan, (18” Tempest) was used
throughout the trials.
Technical
measuring apparatus was supplied and controlled by the University of Central
Lancashire.
Each
experiment house was instrumented using thermocouples (temperature measurement),
and a gas analysis probe. Thermal imaging equipment was also utilised inside and
outside the properties. A digital camera was used to create a photographic
record of events.
Wind
velocity for each experiment was measured with a Vane Anemometer. The wind
conditions were gusting light throughout the week, consequently the wind was
considered to have had a negligible effect and are ignored in the analysis
below.
3.1 Overview
The
experiments were to take place over three days, Tuesday, Wednesday and Thursday.
Each experiment was repeated using both defensive tactics and offensive tactics.
It had been decided that time was available to carry out three experiments per
day. Consequently, the third experiment each day was set aside to enable a
repeat experiment to be carried out in light of what had happened on the first
two experiments.
Due
to a very high level of interest shown by the media, it was decided that the
final day, Friday, should be considered as a press day to allow demonstrations
and interviews to take place. The reason for this was to ensure that the
experiments could take place Tuesday, Wednesday and Thursday without
interruption. Some experimenting however did take place on the Friday and is
included in this project.
The
experiments are described in the order that they took place. Included in the
description are the graphs drawn from thermocouple and gas data, and the visual
observations of the fire-fighters involved.
3.2 Events
of 10th January 2000
The
Monday of the experiment week was given over to preparation. The venue was
visited for the purpose of carrying out a final assessment of the site. The
following tasks were carried out:
·
A final health and safety risk
assessment check
·
An initial inspection by the technical
support!team
·
Collection of furniture from storage
·
Preparation of the first experiment
house for technical apparatus
·
Collection of fire-fighting equipment
3.3 Events of 11th January 2000
Fire
crews arrive to find a well-developed front room (lounge) fire. The objective of
the fire crews is to enter the premises through the rear door wearing breathing
apparatus, and extinguish the fire using standard operating procedure.
Objective:
To
develop a well-established single room fire and to measure the temperatures in
and around the fire compartment. To measure the temperatures and gas levels in a
bedroom adjacent to the fire compartment. To establish the effects of defensive
positive pressure ventilation fire-fighting tactics on such a fire.
A
fire was started in a sofa in the lounge. The fire loading in the lounge was
similar to that which would be expected in a real situation. Once the fire was
lit, the fire was allowed to develop until such time as was considered necessary
before fire crews were instructed to enter and tackle the blaze. Within the
house, only the door to the lounge and the door to the bedroom were open. All
external doors and windows were closed.
Parameters
|
T0 |
Entry |
Attack |
Vented |
Fan
on |
Vent(m2)
Inlet
Outlet
|
|
|
150c |
210sec |
240sec |
380sec |
400sec |
1.6 |
0.62 |
Results/Analysis
Refer
to graphs 1A1 – 1A5
Fire
compartment temperatures peaked at around 10000c and then decayed
rapidly, probably due to the fire becoming ventilation controlled. The fire
intensified slightly when the rear door was opened. On application of water the
temperatures within the fire compartment reduced only minimally, hovering around
5000c. Temperatures within the bedroom reached more than 5000c.
Compartment temperatures only dropped rapidly when the fan was applied.
The
thermocouple tree indicates that the neutral plane, (base of smoke layer), was
somewhere in the region of 900-1200mm from floor level at the most intense
period of burning.
The
gas analysis shows that the atmosphere would not have sustained life until
ventilation commenced. CO levels (measured in the bedroom at bed height),
reached 28000 parts per million – the highest levels reached during these
experiments. Once the fan was applied the CO levels dropped rapidly and the O2
levels increased from 10% to 20% within 30 seconds.
Visual
Observation
Flames
were apparent in the early stages, but appeared to be subdued by the smoke
levels. On venting, there was a large quantity of grey smoke. The rate of
exhaustion of this smoke increased markedly on application of the fan.
Observation
of the post-fire scene showed that there was much combustible material remaining
in the fire compartment.
3.3.2
Experiment 1B
Scenario
– offensive positive pressure ventilation
Fire
crews arrive to find a well-developed front room (lounge) fire. The objective of
the fire crews was to enter the premises through the rear door wearing breathing
apparatus, and extinguish the fire using offensive positive pressure ventilation
tactics.
Objective:
To
develop a well-established single room fire and to measure the temperatures in
and around the fire compartment. To measure the temperatures and gas levels in a
bedroom adjacent to the fire compartment. To establish the effects of offensive
positive pressure ventilation fire-fighting tactics on such a fire, and compare
the results to those of the previous experiment.
A
fire was started in a sofa in the lounge. The fire loading in the lounge was
similar to that which would be expected in a real situation. Once the fire was
lit, the fire was allowed to develop until such time as was considered necessary
before the fire compartment was vented and the fan was applied via the rear
door. Fire crews were then instructed to enter and tackle the blaze. Within the
house, only the door to the lounge and the door to the bedroom were open. All
external doors and windows were closed.
Parameters
|
T0 |
Vented |
Fan
on |
Entry |
Attack |
Vent(m2)
Inlet
Outlet |
|
|
160c |
230sec |
240sec |
260sec |
290sec |
1.6 |
0.47 |
Results/Analysis
Refer
to graphs 1B1 – 1B5
Again
the fire appears to have developed rapidly although temperatures were lower,
peaking at around 7500c, than in Experiment 1A. The fire was in decay
when fire-fighting operations began. No fire growth occurred on venting or
applying the fan. The fire has appeared to die down on its own accord, possibly
due to the lack of ventilation causing a smothering effect, the fire was
probably smouldering and the smoke mixture in the compartment was possibly very
fuel-rich, although when the fan was operated there wasn’t sufficient energy
in the fire to create ignition. It is possible that backdraught conditions were
achieved here and if the fan had been applied moments earlier then perhaps a
backdraught would have occurred.
Some
cooling was apparent on application of the fan, particularly at the probes on
the entrance to the bedroom and on the thermocouple tree on the internal fire
compartment doorframe. The neutral plane appears to have not reached a level
quite as low as test 1A, reaching somewhere between 1200 – 1500mm from the
floor.
The
gas analysis shows a similar profile to the previous experiment, with a dramatic
improvement of conditions on application of the fan. CO levels peaked at
approximately 15000 parts per million. The improvement in O2 levels
was slower than in the first experiment.
Visual
Observations
The
fire fighting crew reported smoke coming back down the hallway, towards the fan.
This may be the cause of the slower improvement in gas levels. It was thought
that this might be due to the exhaust vent being to small, creating an
overpressure in the compartment. The vent ratio was 3.4:1 in favour of the
inlet.
3.3.3
Experiment 1C
Scenario
– offensive positive pressure ventilation
The
previous experiment, 1B, was repeated this time using a larger vent size. The
reason for this was to see if the vent restriction was the cause of the smoke
returning down the corridor.
Parameters
|
T0 |
Vented |
Fan
on |
Entry |
Attack |
Vent(m2)
Inlet
Outlet |
|
|
160c |
230sec |
240sec |
260sec |
295sec |
1.6 |
1.0 |
Results/Analysis
Refer
to graphs 1C1 – 1C5
A
similar fire profile was achieved although this time the fire intensified on
venting and application of the fan. The intensification in terms of temperature
was only in the region of 750c. The rate of growth due to this was,
although observed for only a short period, no greater, perhaps even less, than
the original growth rate prior to venting
The
neutral plane came somewhere between 600 – 900mm, lower than in the previous
test. On application of the fan, the neutral plane appears to have risen,
perhaps as high as 1500mm.
The
gas analysis showed a quicker improvement in conditions. The vent ratio for this
test was 1.6:1,
Visual
Observation
No
report!was made of smoke or flame in the corridor. The conditions on the
approach to the fire compartment were cooler and very much clearer than in the
previous experiment. The fire fighters were very impressed with the operation.
3.4 Events of 12th
January
3.4.1
Experiment 2A
Fire
crews arrive to find a well-developed bedroom fire. The objective of the fire
crews is to enter the premises through the rear door wearing breathing
apparatus, and extinguish the fire using standard operating procedure.
Objective:
To
develop a well-established single room fire and to measure the temperatures in
and around the fire compartment. To measure the temperatures and gas levels in
the hallway adjacent to the fire compartment. To establish the effects of
defensive positive pressure ventilation fire-fighting tactics on such a fire.
A
fire was started in bedding materials in the bedroom. The fire loading in the
bedroom was similar to that which would be expected in a real situation. Once
the fire was lit, the fire was allowed to develop until such time as was
considered necessary before firecrews were instructed to enter and tackle the
blaze. Within the house, only the door to the lounge and the door to the bedroom
were open. All external doors and windows were closed. Temperature probes were
fitted to the vent.
Parameters
|
T0 |
Entry |
Attack |
Vented |
Fan
on |
Vent(m2)
Inlet
Outlet |
|
|
170c |
1125sec |
1155sec |
1180sec |
1195sec |
1.6 |
0.67 |
Results/Analysis
Refer
to graphs 2A1 – 2A5
Comparatively
low temperatures were achieved with this fire (3600c). Due to the
nature of the combustible materials the fire growth rate was much slower than
that achieved on the previous day.
The
neutral plane was clearly exhibited on the graphs, being between 900 – 1200mm
from the floor. The high temperatures recorded at the vent are thought to be due
to localised burning observed at the window frame by the fire fighters.
Low
gas levels were also exhibited. The combustible materials were predominantly
bedding and the mattress of the bed.
Visual
Observations
This
experiment was visually observed from the hallway by the author using Breathing
Apparatus. The application of the fan, even when the fire was extinguished, had
a dramatic effect on conditions. There was an instant cooling effect, a fire
compartment immediately after a fire attack is very hot and humid. There was
also a dramatic improvement in visibility; ppv created a far more comfortable
environment for the fire fighters.
3.4.2
Experiment 2B
Scenario
– offensive positive pressure ventilation
Fire
crews arrive to find a well-developed bedroom fire. The objective of the fire
crews was to enter the premises through the rear door wearing breathing
apparatus, and extinguish the fire using offensive positive pressure ventilation
tactics.
Objective:
To
develop a well-established single room fire and to measure the temperatures in
and around the fire compartment. To measure the temperatures and gas levels in
the hallway adjacent to the fire compartment. To establish the effects of
offensive positive pressure ventilation fire-fighting tactics on such a fire,
and compare the results to those of the previous experiment.
A
fire was started in bedding materials in the bedroom. The fire loading in the
bedroom was similar to that which would be expected in a real situation. Once
the fire was lit, the fire was allowed to develop until such time as was
considered necessary before the fire compartment was vented and the fan was
applied via the rear door. Fire crews were then instructed to enter and tackle
the blaze. Within the house, only the door to the lounge and the door to the
bedroom were open. All external doors and windows were closed.
Parameters
|
T0 |
Vented |
Fan
on |
Entry |
Attack |
Vent(m2)
Inlet
Outlet |
|
|
170c |
1715sec |
1725sec |
1745sec |
1775sec |
1.6 |
0.67 |
Results/Analysis
Refer
to graphs 2B1 – 2B4
The
fan appears to have been applied as the fire growth rate was accelerating and
does not appear to have increased this rate noticeably. There was a rapid
decrease in the hallway temperatures on application of the fan, although this
cooling rate was arrested momentarily. Maximum compartment temperatures reached
8000c.
The
thermocouple tree shows a similar result to that of earlier experiments, in that
the neutral plane rose. In this case the rise was very clear, from between 900
– 1200mm to between 1200 – 1500mm on application of the fan.
Surprisingly
low gas levels were recorded again in this fire, but the decrease in gas levels
followed the same profile as the hallway temperatures. Vent temperatures dropped
at some probes and increased at others, with no clear pattern.
Visual
Observation
This
experiment was visually observed from the hallway by the author. Conditions in
the hallway prior to positive pressure ventilation were hot and very
smoke-logged. On application of the fan the corridor became cooler and clear
very quickly. This made the approach to the fire compartment comparatively
straightforward.
At
some point between the fan being used and the fire being attacked, flames were
observed coming out of the fire compartment and across the hall at head height.
Indications of fire spread outside the fire compartment were identified due to
this and the graphs also record data that could be attributed to such an event.