Report!on PPV Trials

at Oxford Road, Preston, U.K.

10 –14 January, 2000

 

Richard Stott B.Eng (Hons),

Assistant Divisional Officer

Lancashire Fire and Rescue Service, U.K.


1.      INTRODUCTION

  1.1    Ventilation

  Ventilation as a fire-fighting tactic has been used since time immemorial.  Hence it is nothing new.  Venting (the creation of exhaust/inlet ports for the products of combustion) a fire has been done with caution, following much training and consequently has been instrumental in reducing property damage and increasing comfort levels for fire-fighters at virtually every fire.  The maxim within the Fire Service has been ‘vent, vent early, but only when safe to do so’.  Hence it has always been recognised that caution is the better part of valour but that used correctly, venting is a key tool in the fire-fighter’s toolbox.

  Positive pressure ventilation is a method of using high volumetric flow rate fans to increase the pressure within a compartment so that the products of combustion are encouraged to exit the compartment in order to reach a region of lower pressure. Generally speaking, the mobile fan unit is placed approximately 3 metres from the doorway, i.e. outside the building, and the air is directed in through the doorway. Positive pressure ventilation can be viewed as simply an advanced use of natural ventilation techniques.

  Positive pressure ventilation is widely utilised in the USA and the concept was first introduced there many years ago. The constructional methods used for buildings in USA differ widely to those of the UK, so it is difficult to justify the direct application of the ventilation techniques developed there.

  However, many local authority Fire Services in Great Britain now use positive pressure ventilation in the post-fire scenario. Most however, are wary regarding the use of positive pressure ventilation prior to the fire being extinguished.  This has been termed ‘aggressive positive pressure ventilation’.  In fact, at the time of writing, only one of the fifty-seven local authority brigades has routinely adopted this approach.

In contrast to the above paragraph, it has been decided to utilise the terms offensive and defensive in this report, to parallel the Home Office and LFRS, with the following definitions(1);

  Defensive – ventilating away from the fire, or after the fire is out.

Offensive - ventilating close to the fire to have a direct effect on the fire itself.

  From hereon, positive pressure ventilation will be referred to as ‘ppv’. With regard to domestic ppv use, as it is very unlikely in a single domestic dwelling that a fan will be used away from the fire, the term defensive should be considered to mean use of ppv once the fire has been extinguished.

  1.2      The Trials

  During the week of 10 – 14 January 2000, Lancashire Fire and Rescue Service, supported by the Department of Built Environment, University of Central Lancashire, undertook a series of ppv trials at Oxford Road, Preston.

  The main objectives of the trials were as follows: -

  ·      To examine the possible tactical advantages of offensive ppv

·      To improve knowledge and skills in the use of defensive ppv

·      To further assess fan selection in terms of fan size

·      To produce a comprehensive report, (including stills and video footage), to assist in future training packages and the further development of operational procedures.

·      To provide realistic, live fire observation for personnel involved.

·      To provide comprehensive data for use in risk assessments.

  The trials were originally planned to take place in two-storey properties but were relocated, due to uncontrollable circumstances to single-storey properties.

 

 

 

Plate 1.  Oxford Road, Avenham

 

Each fire experiment room was furnished with the type of materials that would be expected with a real incident i.e. carpets, curtains, sofas, bedding etc. Consequently, the trials were possibly the most realistic, in terms of fire loading, to have been carried out to date in the U.K.

The trials took place over five days. The chosen approach was to carry out each scenario twice, once using standard fire fighting techniques, (defensive) and once using offensive positive pressure ventilation.

  Although much quantitative data was gathered, the nature of fire, with its many variables, dictates that qualitative data is very important. Consequently, each volunteer has been canvassed for his or her experiences during the trials. This information is included within the report.

  This report!is a précis of a more detailed and technical engineering analysis, which is available if so required.

  1.3      Positive Pressure Ventilation

  Extensive research has been undertaken regarding the subject of positive pressure ventilation and its applications for the Fire Service. Lancashire Fire and Rescue Service and several other Brigades have conducted ‘in house’ experiments to determine the effectiveness of positive pressure ventilation post fire, as a result, the use and safe application at incidents is well documented. 

  Supporters of the use of ppv offensively claim that it has a number of advantages, such as:

  ·        The enhancement of fire-fighter safety due to the improved atmosphere that positive pressure ventilation can create.

  ·        The rapid improvement of conditions remote from the fire-affected compartment will enhance the chances of survival for persons trapped in a building on fire.

  ·        Fire-fighting operations can be expedited as the improved conditions enable the fire attack to take place quicker.

  ·        The correct use of positive pressure ventilation prevents firespread beyond the fire compartment.

  The literature review undertaken for this project demonstrates that although research into positive pressure ventilation has been fragmented, the overall picture is one of support!for the technique. There is a distinct lack of formal academic evidence to support!this however and consequently many sceptical Chief Fire Officers, this being demonstrated by the reticence of UK Fire Brigades in offensive positive pressure ventilation use. Most of the reports reviewed indicate the need for further research.

  Two Fire Brigades have already undertaken offensive ppv experiments, Tyne and Wear Metropolitan Fire Brigade and Greater Manchester County Fire Brigade.  The results of the two sets of experiments undertaken by Tyne & Wear indicate that the use of ppv does not seriously intensify fire spread (2). In contrast to this the report!of offensive ppv experiments in Greater Manchester indicate a rapid acceleration of the fires involved on operation of the fans (3).

  Clearly from the differing results produced by two large Metropolitan Brigades the use of offensive ppv warrants further investigation and research. It is universally accepted that without proper training and correct tactical deployment at incidents, ppv could prove potentially fatal for fire fighters and members of the public.

  When assessing the use of positive pressure ventilation there is a tendency to forget that pressurisation has been incorporated within building designs for several decades. Heating ventilation and air conditioning systems can be designed so that, in the event of a fire, they can be used as a smoke control system. Separate heat and smoke control systems are also designed for the larger building and for certain industrial applications, therefore the concept of ppv and fire application is not a new one.

 

  1.4 Previous U.K. Research -- Overview

  A major concern amongst fire officers and the research establishment in this country is the fact that ppv may prove ineffective when used offensively, possibly even dangerous. Ventilation techniques for domestic dwellings and small industrial units in the UK have relied on the available openings of the building involved in fire, windows, doors, or occasionally roof lights are used when appropriate to exhaust the contaminants. The problem foreseen initially with ppv in UK construction buildings is the lack of available or adequate exhaust points to compensate for the amount of air entering the building from the ventilation units.  Flashover, backdraught and firespread were all perceived problems associated with the fans in early assessments.  

  Early in 1994, Warrington fire research consultants undertook a survey of ventilation when used as a fire-fighting tactic; the report!from the survey was published later that year. The report!concluded that further research needed to be undertaken on the subject of ppv ventilation since little or no research existed in the UK. As a result of the Warrington report!the Fire Experimental Unit at Moreton in Marsh undertook a further research project, this work to be backed up by a survey of the expertise available in the USA and other countries (4).

  The research results indicated that ppv to be particularly suited to fire attack in small domestic dwellings however, caution was expressed regarding its use (ppv) due to the ‘significant amount of additional training’ that would be required.

  Two trials of note were conducted by the Fire Experimental Unit using the Fire Service College’s facilities; the first using fires on the ground floor and the second experiment consisted of fires in a basement.

 

The results of these experiments demonstrated the need for a systematic ventilation procedure when using ppv. It was found that any compartment where an outside window was not opened was effectively sealed by the ppv, preventing any smoke clearance. Where ppv was not used the compartment cleared gradually, but this did not happen with ppv. The main conclusion from this experiment is that if using ppv for smoke clearance, rooms should be cleared one at a time and once a room is clear of smoke, the windows should then be closed. The report!further concludes that these results were due to the limited flow from the portable ventilation units and that ppv was not as effective in clearing rooms with upwind windows.

  Another very important point to be concluded from the Experimental Unit’s experiments was the fact that ppv can easily be overcome by a strong wind therefore its use is limited to certain scenarios.

  A comprehensive research document was produced by J G Rimen (5), which researched the use of positive pressure ventilation in domestic properties. The document describes a series of trials conducted in still air conditions and a further series of trials conducted in a four bedroom detached house. J.G Rimen had listened to the views of Fire Officers and others in the building industry and acknowledged the sceptics who regarded increasing the oxygen content to fires via ppv as dangerous.

  A series of trials were undertaken in a ‘mock’ detached dwelling, the primary objective being to determine basic rules for the use of ppv at incidents. The results obtained during the trials were recorded using a data logger and the results subsequently analysed.

  The report!concluded that an inlet / outlet ratio of 2 / 1 is the ideal ratio for the use of ppv and this is what Brigades should aim for. If this ratio is unable to be obtained then it would be still advantageous to have the inlet opening larger than the outlet opening. Experiments undertaken also suggest an optimum distance of 1.0m from the inlet opening for the fan and that it was not necessary to seal the opening with the fan, this last conclusion contradicts current working practises which have been adopted from other research. Another conclusion from the report!indicates that the most efficient method of using the ppv fan is when it is placed so that air is projected horizontally into the building.

  The research conclusions indicate that ppv has the capability of rapidly improving the environment at fires, but can also make things worse and that it is virtually impossible to predict with any certainty the effect of the fan in a given circumstance. This particular conclusion from the report!was used to back up the evidence of those individuals opposed to the adoption of ppv for fire service operations.

  Others adopted a totally opposing opinion within the UK fire service for ppv application as a result of J.G Rimen’s report. The report!states that ‘each fire situation, and specifically whether or not to deploy ppv, would need to be considered on its particular merits’, in other words risk assessment. Those in favour of ppv use argue that a ventilation fan is just another piece of equipment available to the incident commander and with adequate training and correct incident assessment, it (ppv) is safe to use.

Fire Authorities in the UK have acknowledged the training requirement for ppv; two metropolitan Brigades have conducted fire experiments to assess the training implications and effectiveness of ppv.

Tyne and Wear Metropolitan Fire Brigade acquired the use of two derelict semi-detached properties; these were subsequently used for tactical ventilation trials in real fire situations during November 1996. The properties used were identical in construction and layout, which enabled fires to be repeated and compared.

Cribs were placed in various rooms within the houses and holes drilled in the walls at various heights to facilitate thermocouples. Temperature readings for all the exercises were recorded and used to compare the effect of ppv in different locations of the houses. Wooden pallets, straw, diesel and paraffin produced the heat and smoke for the experiments with maximum temperatures reaching around 800°C.

The experiments from Tyne and Wear are summarised as follows (6):

·        Experiments carried out indicated ppv would overcome wind strengths of 8-10m/s, the experiments carried out by the experimental unit at Moreton showed ppv to be ineffective against a 2m/s wind.

·        Ppv did not seriously intensify or spread a fire however some localised flaming did occur.

·        Ppv improves visibility in a short time scale.

·        Ppv reduces temperatures dramatically in a short period of after application.

·        Effective use of ppv improves the working environment and reduces the risk of flashover.

The Tyne and Wear report!recommends the defensive use of ppv and appears positive regarding the use of ppv offensively.

  On 1st May 1998 Greater Manchester Fire Service carried out a series of tests using disused terraced properties. The objectives for the tests were to document and develop the behaviour of fire using offensive positive pressure ventilation, the results to be used for the formulation of Brigade training policy. The tests were carried out with assistance from the University of Central Lancashire, who produced the report(7) from which this information is drawn.

  Three main tests were carried out; a bedroom fire, with a vent made prior to application of the fan, a bedroom fire without a vent, a lounge fire with vent made after application of the fan.

 

Equipment from the University Of Central Lancashire was used to measure temperatures, gas compositions and fire growth in a similar manner to the Tyne and Wear experiments. Video cameras erected outside the buildings observed the smoke movement from the exhaust points whilst a thermal imaging camera was used to show heat transfer and fire spread internally.

  With these tests the fire was not confined to a crib and sufficient materials were present to support!flashover. The fire load consisted of upholstered furniture and chipboard that were arranged to simulate the furniture and fittings of a typical room.

  During all the tests, the application of PPV produced higher temperatures within the fire compartment after an initial decrease. It should be mentioned, however, that two of the tests were deliberately arranged so that ppv was used incorrectly.

  In the first test, the compartment (internal) door was open until it was considered the fire had almost reached the fully developed stage, and then the door was closed. The graph indicated that the fire had become strongly ventilation controlled by these actions, dropping from a temperature of 7000c to just over 200. The room was then vented, by breaking the window and opening the internal door, prior to applying the ppv fan.

 

The same criticism can be applied to each of the tests carried out i.e. it cannot be concluded that ppv accelerated the fire any more than natural ventilation alone would achieve.

 

During all the tests a visible ‘flashback’ was reported on application of ppv. The timing of this event for each test is unclear and no evidence is apparent on the graphs. No reference had been made to this effect before and consequently it is an interesting area for consideration.

There are a number of possible reasons for this effect:

 

bulletThe fire may be undergoing transition from growth to fully developed, this transition is rapid; the fire wants a large volume of oxygen which results in lengthened flames. The fire nearly always becomes ventilation controlled at this stage.
bulletThe fire compartment pressure due to buoyancy is in excess of that in the doorway.
bulletThere is too restrictive a vent to outside; the fire had nowhere else to go.
bulletThe fire was affected by wind from outside.

 

 

The data from Tyne and Wear does highlight a small localised increase in temperatures after ppv application, but does not mention the possibility of a ‘flashback’ on initial application, the report!does acknowledge the potential danger of offensive use.

 

In July 1998, Tyne and Wear Fire Brigade carried out a further set of trials at the Fire Service College. The trials were conducted in conjunction with the Fire Experimental Unit of the Home Office. The brief for these tests was to establish the effects of ppv on a casualty situated between the fire and the vent, and the effect of ppv on fire spread, two issues perceived at the time to be holding ppv use back.

 

The report(8) of the trials, produced by the Fire Research and Development Group, concludes; ‘ppv produced no measurable difference in fire spread from that observed under natural ventilation alone. However ventilation, whether natural or forced, did appear to increase fire spread.’

 

This was an interesting conclusion which again conflicts with the findings from GMC.

 

Note:  the performance of positive pressure ventilation fans has improved rapidly since their inception. Many of the early trials used fans that were of low output and consequently some results may be misleading.


1.      Preston Fire Trials

 

2.1      The Properties

 

The properties used for the trials were a connected block of single-storey, two and three bedroom flats, built circa 1970. The block was scheduled for demolition the week following the trials. The properties had been donated for use by Collingwood Housing Association.

 

The construction of the properties was mainly of concrete, which proved ideal for repeatable experiments.

Plan drawings of the properties are included in Appendix A

 

2.2  Equipment and Technical Apparatus

 

Appliances and general firefighting equipment was provided by Lancashire Fire and Rescue Service.

 

Positive pressure ventilation fans were supplied by FSE Ltd. The company supplied a range of fans for use but for consistency the same fan, (18” Tempest) was used throughout the trials.

 

Technical measuring apparatus was supplied and controlled by the University of Central Lancashire.

 

Each experiment house was instrumented using thermocouples (temperature measurement), and a gas analysis probe. Thermal imaging equipment was also utilised inside and outside the properties. A digital camera was used to create a photographic record of events.

 

Wind velocity for each experiment was measured with a Vane Anemometer. The wind conditions were gusting light throughout the week, consequently the wind was considered to have had a negligible effect and are ignored in the analysis below.

 

 

3          Experiments

 

3.1  Overview

 

The experiments were to take place over three days, Tuesday, Wednesday and Thursday. Each experiment was repeated using both defensive tactics and offensive tactics. It had been decided that time was available to carry out three experiments per day. Consequently, the third experiment each day was set aside to enable a repeat experiment to be carried out in light of what had happened on the first two experiments.

 

Due to a very high level of interest shown by the media, it was decided that the final day, Friday, should be considered as a press day to allow demonstrations and interviews to take place. The reason for this was to ensure that the experiments could take place Tuesday, Wednesday and Thursday without interruption. Some experimenting however did take place on the Friday and is included in this project.

 

The experiments are described in the order that they took place. Included in the description are the graphs drawn from thermocouple and gas data, and the visual observations of the fire-fighters involved.

 

3.2  Events of 10th January 2000

 

The Monday of the experiment week was given over to preparation. The venue was visited for the purpose of carrying out a final assessment of the site. The following tasks were carried out:

 

·        A final health and safety risk assessment check

·        An initial inspection by the technical support!team

·        Collection of furniture from storage

·        Preparation of the first experiment house for technical apparatus

·        Collection of fire-fighting equipment

 

 

3.3 Events of 11th January 2000

 

3.3.1  Experiment 1A

 

Scenario – defensive positive pressure ventilation

 

Fire crews arrive to find a well-developed front room (lounge) fire. The objective of the fire crews is to enter the premises through the rear door wearing breathing apparatus, and extinguish the fire using standard operating procedure.

 

Objective:

 

To develop a well-established single room fire and to measure the temperatures in and around the fire compartment. To measure the temperatures and gas levels in a bedroom adjacent to the fire compartment. To establish the effects of defensive positive pressure ventilation fire-fighting tactics on such a fire.

 

A fire was started in a sofa in the lounge. The fire loading in the lounge was similar to that which would be expected in a real situation. Once the fire was lit, the fire was allowed to develop until such time as was considered necessary before fire crews were instructed to enter and tackle the blaze. Within the house, only the door to the lounge and the door to the bedroom were open. All external doors and windows were closed.

 

Parameters

T0

Entry

Attack

Vented

Fan on

  Vent(m2)

   Inlet       Outlet                

150c

 

210sec

240sec

380sec

400sec

1.6

0.62

 

 

Results/Analysis

 

Refer to graphs 1A1 – 1A5

 

Fire compartment temperatures peaked at around 10000c and then decayed rapidly, probably due to the fire becoming ventilation controlled. The fire intensified slightly when the rear door was opened. On application of water the temperatures within the fire compartment reduced only minimally, hovering around 5000c. Temperatures within the bedroom reached more than 5000c. Compartment temperatures only dropped rapidly when the fan was applied.

 

The thermocouple tree indicates that the neutral plane, (base of smoke layer), was somewhere in the region of 900-1200mm from floor level at the most intense period of burning.

 

The gas analysis shows that the atmosphere would not have sustained life until ventilation commenced. CO levels (measured in the bedroom at bed height), reached 28000 parts per million – the highest levels reached during these experiments. Once the fan was applied the CO levels dropped rapidly and the O2 levels increased from 10% to 20% within 30 seconds.

 

Visual Observation

 

Flames were apparent in the early stages, but appeared to be subdued by the smoke levels. On venting, there was a large quantity of grey smoke. The rate of exhaustion of this smoke increased markedly on application of the fan.

 

Observation of the post-fire scene showed that there was much combustible material remaining in the fire compartment.

3.3.2  Experiment 1B

 

Scenario – offensive positive pressure ventilation

 

Fire crews arrive to find a well-developed front room (lounge) fire. The objective of the fire crews was to enter the premises through the rear door wearing breathing apparatus, and extinguish the fire using offensive positive pressure ventilation tactics.

 

Objective:

 

To develop a well-established single room fire and to measure the temperatures in and around the fire compartment. To measure the temperatures and gas levels in a bedroom adjacent to the fire compartment. To establish the effects of offensive positive pressure ventilation fire-fighting tactics on such a fire, and compare the results to those of the previous experiment.

 

A fire was started in a sofa in the lounge. The fire loading in the lounge was similar to that which would be expected in a real situation. Once the fire was lit, the fire was allowed to develop until such time as was considered necessary before the fire compartment was vented and the fan was applied via the rear door. Fire crews were then instructed to enter and tackle the blaze. Within the house, only the door to the lounge and the door to the bedroom were open. All external doors and windows were closed.

 

Parameters

 

T0

Vented

Fan on

Entry

Attack

Vent(m2)

   Inlet          Outlet

160c

 

230sec

240sec

260sec

290sec

1.6

0.47

 

Results/Analysis

 

Refer to graphs 1B1 – 1B5

 

Again the fire appears to have developed rapidly although temperatures were lower, peaking at around 7500c, than in Experiment 1A. The fire was in decay when fire-fighting operations began. No fire growth occurred on venting or applying the fan. The fire has appeared to die down on its own accord, possibly due to the lack of ventilation causing a smothering effect, the fire was probably smouldering and the smoke mixture in the compartment was possibly very fuel-rich, although when the fan was operated there wasn’t sufficient energy in the fire to create ignition. It is possible that backdraught conditions were achieved here and if the fan had been applied moments earlier then perhaps a backdraught would have occurred.

 

Some cooling was apparent on application of the fan, particularly at the probes on the entrance to the bedroom and on the thermocouple tree on the internal fire compartment doorframe. The neutral plane appears to have not reached a level quite as low as test 1A, reaching somewhere between 1200 – 1500mm from the floor.

 

The gas analysis shows a similar profile to the previous experiment, with a dramatic improvement of conditions on application of the fan. CO levels peaked at approximately 15000 parts per million. The improvement in O2 levels was slower than in the first experiment.

Visual Observations

 

The fire fighting crew reported smoke coming back down the hallway, towards the fan. This may be the cause of the slower improvement in gas levels. It was thought that this might be due to the exhaust vent being to small, creating an overpressure in the compartment. The vent ratio was 3.4:1 in favour of the inlet.

 

 

3.3.3  Experiment 1C

 

Scenario – offensive positive pressure ventilation

 

The previous experiment, 1B, was repeated this time using a larger vent size. The reason for this was to see if the vent restriction was the cause of the smoke returning down the corridor. 

 

Parameters

T0

Vented

Fan on

Entry

Attack

Vent(m2)

    Inlet           Outlet

160c

 

230sec

240sec

260sec

295sec

1.6

1.0

 

Results/Analysis

 

Refer to graphs 1C1 – 1C5

 

A similar fire profile was achieved although this time the fire intensified on venting and application of the fan. The intensification in terms of temperature was only in the region of 750c. The rate of growth due to this was, although observed for only a short period, no greater, perhaps even less, than the original growth rate prior to venting

 

The neutral plane came somewhere between 600 – 900mm, lower than in the previous test. On application of the fan, the neutral plane appears to have risen, perhaps as high as 1500mm.

 

The gas analysis showed a quicker improvement in conditions. The vent ratio for this test was 1.6:1,

 

Visual Observation

 

No report!was made of smoke or flame in the corridor. The conditions on the approach to the fire compartment were cooler and very much clearer than in the previous experiment. The fire fighters were very impressed with the operation.

 

3.4 Events of 12th January

 

3.4.1  Experiment 2A

 

Scenario – defensive positive pressure ventilation

 

Fire crews arrive to find a well-developed bedroom fire. The objective of the fire crews is to enter the premises through the rear door wearing breathing apparatus, and extinguish the fire using standard operating procedure.

 

Objective:

 

To develop a well-established single room fire and to measure the temperatures in and around the fire compartment. To measure the temperatures and gas levels in the hallway adjacent to the fire compartment. To establish the effects of defensive positive pressure ventilation fire-fighting tactics on such a fire.

 

A fire was started in bedding materials in the bedroom. The fire loading in the bedroom was similar to that which would be expected in a real situation. Once the fire was lit, the fire was allowed to develop until such time as was considered necessary before firecrews were instructed to enter and tackle the blaze. Within the house, only the door to the lounge and the door to the bedroom were open. All external doors and windows were closed. Temperature probes were fitted to the vent.

 

Parameters

T0

Entry

Attack

Vented

Fan on

  Vent(m2)  

 

 Inlet          Outlet   

170c

 

1125sec

1155sec

1180sec

1195sec

1.6

0.67

 

 

Results/Analysis

 

Refer to graphs 2A1 – 2A5

 

Comparatively low temperatures were achieved with this fire (3600c). Due to the nature of the combustible materials the fire growth rate was much slower than that achieved on the previous day.

 

The neutral plane was clearly exhibited on the graphs, being between 900 – 1200mm from the floor. The high temperatures recorded at the vent are thought to be due to localised burning observed at the window frame by the fire fighters.

 

Low gas levels were also exhibited. The combustible materials were predominantly bedding and the mattress of the bed.

 

Visual Observations

 

This experiment was visually observed from the hallway by the author using Breathing Apparatus. The application of the fan, even when the fire was extinguished, had a dramatic effect on conditions. There was an instant cooling effect, a fire compartment immediately after a fire attack is very hot and humid. There was also a dramatic improvement in visibility; ppv created a far more comfortable environment for the fire fighters.

 

 

 

3.4.2  Experiment 2B

 

Scenario – offensive positive pressure ventilation

 

Fire crews arrive to find a well-developed bedroom fire. The objective of the fire crews was to enter the premises through the rear door wearing breathing apparatus, and extinguish the fire using offensive positive pressure ventilation tactics.

 

Objective:

 

To develop a well-established single room fire and to measure the temperatures in and around the fire compartment. To measure the temperatures and gas levels in the hallway adjacent to the fire compartment. To establish the effects of offensive positive pressure ventilation fire-fighting tactics on such a fire, and compare the results to those of the previous experiment.

 

A fire was started in bedding materials in the bedroom. The fire loading in the bedroom was similar to that which would be expected in a real situation. Once the fire was lit, the fire was allowed to develop until such time as was considered necessary before the fire compartment was vented and the fan was applied via the rear door. Fire crews were then instructed to enter and tackle the blaze. Within the house, only the door to the lounge and the door to the bedroom were open. All external doors and windows were closed.

 

Parameters

T0

Vented

Fan on

Entry

Attack

Vent(m2)

    Inlet           Outlet

170c

 

1715sec

1725sec

1745sec

1775sec

1.6

0.67

 

 

Results/Analysis

Refer to graphs 2B1 – 2B4

 

The fan appears to have been applied as the fire growth rate was accelerating and does not appear to have increased this rate noticeably. There was a rapid decrease in the hallway temperatures on application of the fan, although this cooling rate was arrested momentarily. Maximum compartment temperatures reached 8000c.

 

The thermocouple tree shows a similar result to that of earlier experiments, in that the neutral plane rose. In this case the rise was very clear, from between 900 – 1200mm to between 1200 – 1500mm on application of the fan.

 

Surprisingly low gas levels were recorded again in this fire, but the decrease in gas levels followed the same profile as the hallway temperatures. Vent temperatures dropped at some probes and increased at others, with no clear pattern.

 

Visual Observation

 

This experiment was visually observed from the hallway by the author. Conditions in the hallway prior to positive pressure ventilation were hot and very smoke-logged. On application of the fan the corridor became cooler and clear very quickly. This made the approach to the fire compartment comparatively straightforward.

 

At some point between the fan being used and the fire being attacked, flames were observed coming out of the fire compartment and across the hall at head height. Indications of fire spread outside the fire compartment were identified due to this and the graphs also record data that could be attributed to such an event.